Specification of Smart3000 -True Sine Wave Serial Number: S01
DC-AC Inverter
|
|
Continuous power
|
3000W + 10%
|
Max. Surge power
|
7000W ± 10%/ 50ms
|
Nominal DC input voltage
|
48 VDC
|
I Standby
|
<= 1500mA
|
AC output voltage range
|
At normal load adjustable: 220V – 240 VAC
|
Frequency
|
50Hz ± 1Hz
|
Output waveform
|
True sine wave, distortion <= 3%
|
Efficiency
|
88% at normal load
|
Power factor
|
Cosj >= 0.8
|
Low voltage disconnect (L.V.D) Factory setting
|
42V ± 3%
|
System Manual reset by AC power switch (Over load, LVD)
|
> 42 V ± 3%
|
UPS Function
|
|
AC Input voltage range
|
180 – 250VAC
|
Frequency
|
50 Hz ± 1Hz
|
Off line UPS, transfer time
|
10 -12 ms
|
AC pass though current
|
13A
|
Search Mode
|
|
I Standby
|
<= 100mA
|
Detect power (on £ 10s, off £ 30s)
|
30W
|
Operation range
|
20 m and using in no special interference
|
DC-DC Converter
|
|
Nominal DC input voltage
|
48 VDC
|
DC operating range
|
42 – 58 VDC
|
DC output voltage
|
12V ± 3%
|
Max. DC output current
|
20A
|
DC protection output
|
>= 20 A (Electronic protection)
|
Battery Charger
|
|
Charge type
|
Sealed gel /AGM
|
Flooded Lead Acid
|
2-Step charger
|
Boost charge
|
56 -57V
|
59 - 60V
|
Float charge (Constant Vol.)
|
55.2V ± 0.5V
|
55.2V ± 0.5V
|
Recharge
|
50.4 ± 0.5V
|
53.2V ± 0.5V
|
Max. Charging current of
AC grid/ generator and DC solar/ wind, hydro, add.
|
20A/ 50A/50A
|
Protection
|
|
Overload AC
|
AC output voltage will be decreased
|
Over temperature, L.V.D
|
AC/DC power cut off
|
Reverse polarity
|
DC fuse protected
|
Charging Sources – Led lighting
|
|
Solar - active
|
Green
|
Wind/ Hydro/ Add - active
|
Green (lighting I charge >= 5A)
|
Grid - active
|
Green
|
Charging - active
|
Orange
|
Battery level monitor
|
|
Full
|
56 -57V / 59 - 60V /Green
|
Normal
|
>= 49.2V ± 2% / Green
|
Low
|
>= 44V ± 2% / Orange
|
Empty
|
<=42V ± 2% / Red
|
Meter/ Fan/ Fuse & others
|
|
DC voltage meter
|
75V
|
AC voltage meter
|
300V
|
AC/DC charging current meter
|
20A/50A/50A – At 48VDC
|
DC fuse input/ DC Breaker/AC Breaker
|
150A/100A /15A
|
Fan
|
7, Thermally controlled
|
Climatic condition
|
10 – 45°C
|
Dimension (L x W x H) mm
|
530 x 424 x 800
|
Weight
|
Appr. 60kgs
|
Regulations
|
|
EC compliance
|
EN60742, 1995; EN50075, 1990; EN55014-1; EN55014-2; EN 61000-3-2; EN61000-3-3; EN50091-1-2,1996; EN60950
|
EC Directives
|
Low-voltage
|
|
|
|